# PSU firmware update
|
||
|
|
|
||
|
|
Author: Lei YU <mine260309@gmail.com> <LeiYU>
|
||
|
|
|
||
|
|
Other contributors: Su Xiao <suxiao@inspur.com> Derek Howard <derekh@us.ibm.com>
|
||
|
|
|
||
|
|
Created: 2019-06-03
|
||
|
|
|
||
|
|
## Problem Description
|
||
|
|
|
||
|
|
There is no support in OpenBMC to update the firmware for PSUs.
|
||
|
|
|
||
|
|
## Background and References
|
||
|
|
|
||
|
|
In OpenBMC, there is an existing interface for [software update][1].
|
||
|
|
|
||
|
|
The update process consists of:
|
||
|
|
|
||
|
|
1. Uploading an image to the BMC;
|
||
|
|
2. Processing the image to check the version and purpose of the image;
|
||
|
|
3. Verifying and activating the image.
|
||
|
|
|
||
|
|
Currently, BMC and BIOS firmware update are supported:
|
||
|
|
|
||
|
|
- [phosphor-bmc-code-mgmt][2] implements BMC code update, and it supports all
|
||
|
|
the above 3 processes.
|
||
|
|
- [openpower-pnor-code-mgmt][3] implements BIOS code update, and it only
|
||
|
|
implements "verifying and activating" the image. It shares the function of the
|
||
|
|
above 1 & 2 processes.
|
||
|
|
- Both of the above use the same [Software DBus interface][1].
|
||
|
|
|
||
|
|
For PSU firmware update, it is preferred to re-use the same function for the
|
||
|
|
above 1 & 2.
|
||
|
|
|
||
|
|
## Requirements
|
||
|
|
|
||
|
|
The PSU firmware shall be updated in the below cases:
|
||
|
|
|
||
|
|
1. The user manually invokes the APIs to do the update;
|
||
|
|
2. After BMC code update and if there is a newer PSU image in the BMC's
|
||
|
|
filesystem, BMC shall update the PSU firmware;
|
||
|
|
3. When a PSU is replaced and the version is older than the one in BMC's
|
||
|
|
filesystem, BMC shall update the PSU firmware.
|
||
|
|
4. An optional 'override' parameter may be specified to do the update in the
|
||
|
|
above cases regardless of which PSU image is newer.
|
||
|
|
5. There are cases that a system could use different models of PSUs, and thus
|
||
|
|
different PSU firmware images need to be supported.
|
||
|
|
|
||
|
|
For some PSUs, it is risky to do PSU code update while the host is running to
|
||
|
|
avoid power loss. This shall be handled by PSU vendor-specific tools, but not in
|
||
|
|
the generic framework.
|
||
|
|
|
||
|
|
Note: The "vendor-specific" referred below is the PSU vendor-specific.
|
||
|
|
|
||
|
|
So the below checks are optional and expected to be handled by vendor-specific
|
||
|
|
tool:
|
||
|
|
|
||
|
|
1. If the host is powered off;
|
||
|
|
2. If the redundant PSUs are all connected;
|
||
|
|
3. If the AC input and DC standby output is OK on all the PSUs;
|
||
|
|
|
||
|
|
## Proposed Design
|
||
|
|
|
||
|
|
As described in the above requirements, there are different cases where the PSU
|
||
|
|
firmware is updated:
|
||
|
|
|
||
|
|
- When the APIs are invoked;
|
||
|
|
- When a new version is updated together with BMC code update;
|
||
|
|
- When a PSU is replaced with an old version of the firmware.
|
||
|
|
|
||
|
|
### Update by API
|
||
|
|
|
||
|
|
This method is usually used by users who manually update PSU firmware.
|
||
|
|
|
||
|
|
It will re-use the current interfaces to upload, verify, and activate the image.
|
||
|
|
|
||
|
|
1. The "Version" interface needs to be extended:
|
||
|
|
- Add a new [VersionPurpose][4] for PSU;
|
||
|
|
- Re-use the existing `ExtendedVersion` as an additional string for
|
||
|
|
vendor-specific purpose, e.g. to indicate the PSU model.
|
||
|
|
2. Re-use the existing functions implemented by [phosphor-bmc-code-mgmt][2] for
|
||
|
|
uploading and processing the image.
|
||
|
|
- The PSU update image shall be a tarball that consists of a MANIFEST,
|
||
|
|
images, and signatures.
|
||
|
|
- When the PSU image is uploaded and processed, a `VersionObject` shall be
|
||
|
|
created to indicate the version and its purpose.
|
||
|
|
3. There will be a new service that implements the [Activation][5] interface to
|
||
|
|
update the PSU firmware.
|
||
|
|
- The service will be started by default when BMC starts;
|
||
|
|
- On start, the service will check the PSU's existing firmware and create the
|
||
|
|
`Version` and `Activation` interfaces.
|
||
|
|
- The service shall watch the interface added on
|
||
|
|
`/xyz/openbmc_project/Software`.
|
||
|
|
- When a new object with PSU `VersionPurpose` is added, the service will
|
||
|
|
verify the signature of the image;
|
||
|
|
- The service shall check the `ExtendedVersion` to make sure the image
|
||
|
|
matches the PSU model.
|
||
|
|
- The service will have a configuration file to describe the PSU model and
|
||
|
|
its related vendor-specific tools.
|
||
|
|
- The service will find the matched vendor-specific tool to perform the code
|
||
|
|
update. For example, if a vendor specific tool `foo` is configured in
|
||
|
|
`psu-update@foo.service` which executes `foo psu.bin`, the service will
|
||
|
|
find the `psu-update@foo.service` and start it by systemd, which performs
|
||
|
|
the update.
|
||
|
|
- When the PSU code update is completed, an informational event log shall be
|
||
|
|
created.
|
||
|
|
- When the PSU code update is completed, the image, MANIFEST, and optionally
|
||
|
|
the signature will be saved to a pre-defined directory in read-write
|
||
|
|
filesystem for future use, in case a new PSU with old firmware is plugged.
|
||
|
|
4. The vendor-specific tool shall run all the checks it needs to be run, before
|
||
|
|
and after the PSU update, and return a status to the above service to
|
||
|
|
indicate the result.
|
||
|
|
5. When the vendor-specific tool returns errors, the PSU update will be aborted
|
||
|
|
and an error event log shall be created.
|
||
|
|
6. During the update, the service shall set the related sensors to
|
||
|
|
non-functional, and when the update is done, it shall set the related sensors
|
||
|
|
back to functional.
|
||
|
|
|
||
|
|
### Update by new BMC image
|
||
|
|
|
||
|
|
When BMC is updated and a new version of PSU firmware is included, it shall be
|
||
|
|
updated to the PSU. This will be done by the same service described above.
|
||
|
|
|
||
|
|
1. On start, the service will check the PSU image, model and version in its
|
||
|
|
filesystem, compare with the ones in PSU hardware and decide if PSU firmware
|
||
|
|
update shall be performed.
|
||
|
|
2. There could be two places containing the PSU images:
|
||
|
|
- The pre-defined directory in read-only filesystem, which is part of BMC
|
||
|
|
image.
|
||
|
|
- The other pre-defined directory in read-write filesystem, which is the
|
||
|
|
location for the saved PSU images by API update. Both places shall be
|
||
|
|
checked and a newer version will be selected to compare with the PSU
|
||
|
|
hardware.
|
||
|
|
3. If PSU update is needed, the service will find the matched vendor-specific
|
||
|
|
tool to perform the code update.
|
||
|
|
4. The following process will be the same as [Update by API].
|
||
|
|
|
||
|
|
### Update on replaced PSU
|
||
|
|
|
||
|
|
When a PSU is replaced, and the firmware version is older than the one in BMC
|
||
|
|
filesystem (or if the optional 'override' parameter is specified), it shall be
|
||
|
|
updated. This will be done by the same service described above.
|
||
|
|
|
||
|
|
1. On start, the service will subscribe to the PropertiesChanged signal to the
|
||
|
|
PSU object path to monitor the PSU presence status. (Or maybe subscribe the
|
||
|
|
InterfacesAdded/Removed signal?)
|
||
|
|
2. When a PSU's presence status is changed from false to true (or the
|
||
|
|
PropertiesChanged event occurs), the service will check the new PSU's model
|
||
|
|
and firmware version to decide if the firmware needs to be updated.
|
||
|
|
3. If yes, the service will find the matched vendor-specific tool to perform the
|
||
|
|
code update.
|
||
|
|
4. The following process will be the same as [Update by API].
|
||
|
|
|
||
|
|
## Alternatives Considered
|
||
|
|
|
||
|
|
### General implementation
|
||
|
|
|
||
|
|
The PSU firmware update could be implemented by separated recipes that only call
|
||
|
|
vendor-specific tools. It will be a bit simpler but loses the unified interface
|
||
|
|
provided by OpenBMC's existing [software update interface][1], and thus it will
|
||
|
|
become difficult to use a standard API to the PSU firmware update.
|
||
|
|
|
||
|
|
### VersionPurpose
|
||
|
|
|
||
|
|
It is possible to re-use the `VersionPurpose.Other` to represent the PSU image's
|
||
|
|
version purpose. But that requires additional information about the image,
|
||
|
|
otherwise, there is no way to tell if the image is for PSU, or CPLD, or other
|
||
|
|
peripherals. A new `VersionPurpose.PSU` is more specific and makes it easier to
|
||
|
|
implement and friendly for the user.
|
||
|
|
|
||
|
|
### Additional string
|
||
|
|
|
||
|
|
The design proposal uses `ExtendedVersion` as the additional string for
|
||
|
|
vendor-specific purpose, e.g. to indicate the PSU model, so the implementation
|
||
|
|
could check and compare if the image matches the PSU model. It is possible to
|
||
|
|
make it optional or remove this additional string, then the implementation will
|
||
|
|
not verify if the image matches the PSU. It could be OK if we trust the user who
|
||
|
|
is uploading the correct image, especially the image shall be signed. But it is
|
||
|
|
always risky in case the image does not match the PSU, and cause unintended
|
||
|
|
damage if the incorrect PSU firmware is updated.
|
||
|
|
|
||
|
|
## Impacts
|
||
|
|
|
||
|
|
This design only introduces a new `VersionPurpose` enum into the dbus
|
||
|
|
interfaces. The newly introduced PSU firmware update service will be a new
|
||
|
|
service that implements existing [Activation][5] interface. There will be new
|
||
|
|
configuration files for the service to:
|
||
|
|
|
||
|
|
- Link the vendor specific tool with PSU models.
|
||
|
|
- Get the sensors related to the PSU.
|
||
|
|
- etc.
|
||
|
|
|
||
|
|
So the impacts are minimal to existing systems.
|
||
|
|
|
||
|
|
## Testing
|
||
|
|
|
||
|
|
It requires the manual tests to verify the PSU code update process.
|
||
|
|
|
||
|
|
- Verify the PSU code update is done on all PSUs successfully;
|
||
|
|
- Verify the PSU code update will fail if the vendor-specific tool fails on
|
||
|
|
pre-condition check, of fails on updating PSU.
|
||
|
|
- Verify the PSU code update is performed after a new BMC image is updated
|
||
|
|
containing a new (or different, if 'override' used) version of PSU firmware.
|
||
|
|
- Verify the PSU code update is performed after a PSU with old (or different, if
|
||
|
|
'override' is used) firmware is plugged in.
|
||
|
|
|
||
|
|
[1]:
|
||
|
|
https://github.com/openbmc/phosphor-dbus-interfaces/tree/master/yaml/xyz/openbmc_project/Software
|
||
|
|
[2]: https://github.com/openbmc/phosphor-bmc-code-mgmt/
|
||
|
|
[3]: https://github.com/openbmc/openpower-pnor-code-mgmt/
|
||
|
|
[4]:
|
||
|
|
https://github.com/openbmc/phosphor-dbus-interfaces/blob/57b878d048f929643276f1bf7fdf750abc4bde8b/xyz/openbmc_project/Software/Version.interface.yaml#L14
|
||
|
|
[5]:
|
||
|
|
https://github.com/openbmc/phosphor-dbus-interfaces/blob/master/yaml/xyz/openbmc_project/Software/Activation.interface.yaml
|