# Remote BIOS Configuration (RBC) via BMC
|
||
|
|
|
||
|
|
Author: Suryakanth Sekar! ssekar
|
||
|
|
|
||
|
|
Other contributors: Jia Chunhui Deepak Kodihalli Patrick Williams
|
||
|
|
|
||
|
|
Created: 19-Nov-2019
|
||
|
|
|
||
|
|
## Problem Description
|
||
|
|
|
||
|
|
Current OpenBMC doesn't provide mechanism to configure the BIOS remotely. This
|
||
|
|
is needed in data center to maintain several systems under same configuration.
|
||
|
|
|
||
|
|
Remote BIOS Configuration provides ability for the user to view and modify BIOS
|
||
|
|
setup configuration parameters remotely via a BMC at any Host state. New BIOS
|
||
|
|
configuration parameters take effect immediately or next system reboot based on
|
||
|
|
the host firmware support model.
|
||
|
|
|
||
|
|
## Background and References
|
||
|
|
|
||
|
|
[1]
|
||
|
|
https://www.dmtf.org/sites/default/files/standards/documents/DSP0247_1.0.0.pdf
|
||
|
|
[2] https://redfish.dmtf.org/schemas/v1/Bios.v1_1_0.json [3]
|
||
|
|
https://redfish.dmtf.org/schemas/v1/AttributeRegistry.v1_3_2.json
|
||
|
|
|
||
|
|
## Requirements
|
||
|
|
|
||
|
|
1. Mechanism to configure BIOS settings remotely over network interface.
|
||
|
|
2. BMC should support the ability to set the value of all BIOS variables to the
|
||
|
|
factory default state.
|
||
|
|
3. Based on the host firmware support model, BMC should support both Immediate
|
||
|
|
Update or Deferred update.
|
||
|
|
4. In deferred model, When the system is in S0, S3, S4 or S5 state. BMC will
|
||
|
|
send the updated BIOS variables on next BIOS boot only. It will not initiate
|
||
|
|
a BIOS boot immediately.
|
||
|
|
5. In immediate model, BMC should send message to the system firmware (BIOS)
|
||
|
|
Whenever settings are changed.
|
||
|
|
6. BMC should support BIOS attribute registry in redfish schema for BIOS
|
||
|
|
configuration.
|
||
|
|
7. BMC should provide secure way for updating BIOS setup password settings.
|
||
|
|
Detailed password handling design -TBD(will be resolve using ARM TrustZone)
|
||
|
|
Ex: Updating the BIOS password should be support only before end of post.
|
||
|
|
8. Remote BIOS configuration daemon should be independent of interface specific
|
||
|
|
data format.
|
||
|
|
9. BMC should able to take default / current settings from host and store &
|
||
|
|
expose that for out of band updates. 10.BMC should provide the new values to
|
||
|
|
the host.
|
||
|
|
|
||
|
|
## Proposed Design
|
||
|
|
|
||
|
|
```
|
||
|
|
+----------------------------------------------------------------------------------------------------------------+
|
||
|
|
| Remote BIOS configuration (RBC) via BMC |
|
||
|
|
| |
|
||
|
|
| |
|
||
|
|
| +-------------+ +-------------+ +--------------------------------+ +-------+ |
|
||
|
|
| | | | | | RBC daemon | | | +----------+ |
|
||
|
|
| | NET/ Tools +<-LAN->+ LAN-IPMID/ +<Dbus->+ | | | |Web client| |
|
||
|
|
| | | | REDFISH | | Provide following Methods | | | | | |
|
||
|
|
| +-------------+ +-------------+ | -SetAttribute() | | | +----^-----+ |
|
||
|
|
| | -GetAttribute() | | | | |
|
||
|
|
| +-------------+ +-------------+ | -VerifyPassword() | | | LAN |
|
||
|
|
| | | | | | -ChangePassword() | | | | |
|
||
|
|
| | HOST/ BIOS +<-KCS->+ HOST-IPMID +<Dbus->+ | |Redfish| +----V-----+ |
|
||
|
|
| | | | | | Properties +<Dbus>+ API | |Redfish & | |
|
||
|
|
| +-----+-------+ +-------------+ | -BaseBIOSTable | | +<-->+BMCWeb | |
|
||
|
|
| | | -PendingAttributes | | | +----^-----+ |
|
||
|
|
| | | -ResetBIOSSettings | | | | |
|
||
|
|
| | | -IsPasswordInitDone | | | | |
|
||
|
|
| | | | | | +----V-----+ |
|
||
|
|
| | | | | | | Redfish | |
|
||
|
|
| | | | | | | Host | |
|
||
|
|
| | | | | | | Interface| |
|
||
|
|
| | +----^-----------------+---------+ +-------+ +----------+ |
|
||
|
|
| | | PendingAttributesUpdated |
|
||
|
|
| | | | Signal |
|
||
|
|
| | | | |
|
||
|
|
| | +----V-----------------V---------+ |
|
||
|
|
| | | PLDM daemon | |
|
||
|
|
| | | Collect the BIOS data & convert| |
|
||
|
|
| +---------MCTP----------------------->| into native D-bus format and | |
|
||
|
|
| | send to the RBC | |
|
||
|
|
| +--------------------------------+ |
|
||
|
|
+----------------------------------------------------------------------------------------------------------------+
|
||
|
|
```
|
||
|
|
|
||
|
|
##Intel uses the following logic
|
||
|
|
|
||
|
|
BIOS send data in as Proprietary format to the BMC via IPMI interface. There are
|
||
|
|
two types of proprietary XML format files in BIOS configuration. Type-0 contain
|
||
|
|
full BIOS variables in XML format. (Generated by BIOS) Type-1 contain modified
|
||
|
|
BIOS variables in XML format. (Generated by BMC)
|
||
|
|
|
||
|
|
BIOS must provide BIOS capability via KCS interface in early boot stage. BIOS
|
||
|
|
must send compressed proprietary XML type 0 file via IPMI command to the BMC.
|
||
|
|
|
||
|
|
IPMI interface should decompress & validate the received XML Type 0. IPMI
|
||
|
|
interface should convert the XML Type 0 into native to D-bus format and send to
|
||
|
|
the RBC daemon.
|
||
|
|
|
||
|
|
During BDS phase in BIOS. BIOS must get the existing XML info from BMC. If XML
|
||
|
|
version/checksum is mismatch or XML Type 0 is not present in BMC, then BIOS must
|
||
|
|
send XML type 0 to the BMC. If XML version and XML checksum matched & pending
|
||
|
|
BIOS attributes list exist (XML Type 1) in BMC then BIOS must get pending BIOS
|
||
|
|
configuration (XML Type 1) from BMC & update in BIOS region and send updated XML
|
||
|
|
Type 0 to the BMC in order to intact again and then BIOS reset the system to
|
||
|
|
reflect the updated values in BIOS boot.
|
||
|
|
|
||
|
|
BIOS have default BIOS settings in BIOS non-volatile memory. BIOS can restore
|
||
|
|
the default BIOS configuration based on the flag setting in OEM IPMI command
|
||
|
|
issued during BIOS booting. So, restore default BIOS configuration can be done
|
||
|
|
by this mechanism.
|
||
|
|
|
||
|
|
RBC daemon should preserve the AllBiosTables, PendingAttributes list in
|
||
|
|
non-volatile storage. Pending attributes list will be cleared whenever new
|
||
|
|
attributes data received.
|
||
|
|
|
||
|
|
```
|
||
|
|
#Intel uses the following logic for BIOS first boot
|
||
|
|
+---------------------------------------------------------------------------------------------------------------------+
|
||
|
|
| |
|
||
|
|
| +-----------------------+ +----------------------------------------------------------------------------+|
|
||
|
|
| | BIOS | | BMC ||
|
||
|
|
| | | | +-------------------------------+ +------------------------------+ ||
|
||
|
|
| | | | |IPMI Interface (kcs) | |RBC daemon Manager | ||
|
||
|
|
| | | | | -Responsible for send /recv | |-Responsible for handling BIOS| ||
|
||
|
|
| | | | | data between BIOS and BMC | | configuration attributes. | ||
|
||
|
|
| | | | | | | -AllBaseAttributes | ||
|
||
|
|
| | | | | | | -Pending Attributes | ||
|
||
|
|
| | | | | | | -FactoryDefaultSetting | ||
|
||
|
|
| | | | | | | -BIOSPwdHashData | ||
|
||
|
|
| | | | +-------------------------------+ +------------------------------+ ||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+ ||
|
||
|
|
| | Set BIOS capability |<---Req-/Res--> | Set the BIOS capability | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |Set BIOS Pwd hash/Seed |<---Req-/Res--> | Forward to the RBC daemon |--dbus-->| Set BIOSPwdHash data. | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |Check factory settings |<---Req-/Res--> | Get the FactoryDefault prop |<-dbus-- | Send FactoryDefaultSettings | ||
|
||
|
|
| |Init the BIOS config | | | | | | ||
|
||
|
|
| |Based on value. | | | | | | ||
|
||
|
|
| |Get the XML Type0 info |<---Req-/Res--> | Provide the XML Type 0 Info | | | ||
|
||
|
|
| |Generate & compress | | | | | | ||
|
||
|
|
| |XML type 0 file | | | Validate the XML Type 0 | |Collect the Attributes Info | ||
|
||
|
|
| | | | | Unzip the XML Type 0 |--dbus-->| AllBaseAttributes | ||
|
||
|
|
| | Send the XML Type 0 |<---Req-/Res--->| Convert into D-bus format | | ||
|
||
|
|
| | via SetPayload command| | | and send to the RBC. | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| | Continue the BIOS boot| | | | | | ||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+ ||
|
||
|
|
| +----------------------------------------------------------------------------+|
|
||
|
|
+---------------------------------------+-----------------------------------------------------------------------------+
|
||
|
|
```
|
||
|
|
|
||
|
|
```
|
||
|
|
#Intel uses the following logic for BIOS reset
|
||
|
|
+---------------------------------------------------------------------------------------------------------------------+
|
||
|
|
| |
|
||
|
|
| +-----------------------+ +----------------------------------------------------------------------------+|
|
||
|
|
| | BIOS | | BMC ||
|
||
|
|
| | | | +-------------------------------+ +------------------------------+ ||
|
||
|
|
| | | | |IPMI Interface (kcs) | |RBC daemon Manager | ||
|
||
|
|
| | | | | -Responsible for send /recv | |-Responsible for handling BIOS| ||
|
||
|
|
| | | | | data between BIOS and BMC | | configuration attributes. | ||
|
||
|
|
| | | | | | | -AllBaseAttributes | ||
|
||
|
|
| | | | | | | -Pending Attributes | ||
|
||
|
|
| | | | | | | -FactoryDefaultSetting | ||
|
||
|
|
| | | | | | | -BIOSPwdHashData | ||
|
||
|
|
+ | | | +-------------------------------+ +------------------------------+ ||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+ ||
|
||
|
|
| |Set BIOS capability |<---Req-/Res--> | Set the BIOS capability | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |Set BIOS Pwd hash/Seed |<---Req-/Res--> | Forward to the RBC daemon |--dbus-->| Set BIOSPwdHash data | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |Check factory settings |<---Req-/Res--> | Get the FactoryDefault prop |<-dbus-- | Send FactoryDefaultSettings | ||
|
||
|
|
| |Init the BIOS config | | | | | | ||
|
||
|
|
| |Based on value. | | | | | | ||
|
||
|
|
| |Get the XML Type 0 info|<---Req-/Res--> | Provide the XML Type 0 Info | | | ||
|
||
|
|
| |Generate & compress | | | | | | ||
|
||
|
|
| |XML type 0 file. | | | | |Collect the Attributes Info | ||
|
||
|
|
| |Check XML file Chksum. | | | Validate the XML Type 0 |--dbus-->| BaseBIOSTable | ||
|
||
|
|
| |If Chksum mismatch |<---Req-/Res--->| Unzip XML Type 0 & convert | | | ||
|
||
|
|
| |then send the payload | | | into D-bus format and send to | | | ||
|
||
|
|
| |via SetPayload. | | | the RBC | | | ||
|
||
|
|
| |Continue the BIOS boot | | | | | | ||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+ ||
|
||
|
|
| +----------------------------------------------------------------------------+|
|
||
|
|
+---------------------------------------+-----------------------------------------------------------------------------+
|
||
|
|
```
|
||
|
|
|
||
|
|
```
|
||
|
|
#Intel uses the following logic for BIOS reset and BMC have new values
|
||
|
|
+---------------------------------------------------------------------------------------------------------------------+
|
||
|
|
| |
|
||
|
|
| +-----------------------+ +----------------------------------------------------------------------------+|
|
||
|
|
| | BIOS | | BMC ||
|
||
|
|
| | | | +-------------------------------+ +------------------------------+ ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| | | | |IPMI Interface (kcs) | |RBC daemon Manager | ||
|
||
|
|
| | | | | -Responsible for send /recv | |-Responsible for handling BIOS| ||
|
||
|
|
| | | | | data between BIOS and BMC | | configuration attributes. | ||
|
||
|
|
| | | | | | | -AllBaseAttributes | ||
|
||
|
|
| | | | | | | -Pending Attributes | ||
|
||
|
|
| | | | | | | -FactoryDefaultSetting | ||
|
||
|
|
| | | | | | | -BIOSPwdHashData | ||
|
||
|
|
+ | | | +-------------------------------+ +------------------------------+ ||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+ ||
|
||
|
|
| |Set BIOS capability |<---Req-/Res--> | Set the BIOS capability | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |Set BIOS Pwd hash/Seed |<---Req-/Res--> | Forward to the RBC daemon |---dbus->| Set BIOSPwdHash data | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |Check factory settings |<---Req-/Res--> | Get the FactoryDefault prop |<--dbus--| Send FactoryDefaultSettings | ||
|
||
|
|
| |Init the BIOS config | | | | | | ||
|
||
|
|
| |Based on value. | | | | | | ||
|
||
|
|
| |Get the XML Type 0 info|<---Req-/Res--> | Provide the XML Type 0 Info | | | ||
|
||
|
|
| |Generate & compress | | | | | | ||
|
||
|
|
| |XML Type 0 file. | | | | | | ||
|
||
|
|
| |Check XML file Chksum. | | | | | | ||
|
||
|
|
| |If Chksum match |<---Req-/Res--->| Provide the XML Type 0 | | | ||
|
||
|
|
| |then get the XML Type 1| | | | | | ||
|
||
|
|
| |via GetPayload. | | | | | | ||
|
||
|
|
| |Get the XML Type 1 | | | | | | ||
|
||
|
|
| |via GetPayload command.|<---Req-/Res--->| Provide the XML Type 1 | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |Update the new value | | | | | | ||
|
||
|
|
| |and new chksum in |<---Req-/Res--->| Get new XML Type 0 & convert |--dbus-->| Collect the Atributes info | ||
|
||
|
|
| |BIOS. | | | into native to D-bus format | | AllBaseAttributes | ||
|
||
|
|
| |Reset the system. | | | | | | ||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+ ||
|
||
|
|
| +----------------------------------------------------------------------------+|
|
||
|
|
+---------------------------------------+-----------------------------------------------------------------------------+
|
||
|
|
|
||
|
|
```
|
||
|
|
|
||
|
|
##BIOS send the data in BIOS configuration PLDM via MCTP
|
||
|
|
|
||
|
|
BIOS should update the BIOS settings via Set BIOS table PLDM command- BIOS
|
||
|
|
string table, Attribute name table, Attribute value table via MCTP.
|
||
|
|
|
||
|
|
RBC daemon should create pending BIOS attributes list based on the user input
|
||
|
|
configuration and send PendingAttributesUpdated signal.
|
||
|
|
|
||
|
|
PLDM daemon should register for PendingAttributesUpdated signal & RBC daemon
|
||
|
|
should generate signal whenever attribute value changed by SetPendingAttributes,
|
||
|
|
set attribute D-bus call. PLDM should Wait for PendingAttributesUpdated signal
|
||
|
|
and pull the pending attributes value from RBC daemon. PLDM should delete the
|
||
|
|
Pending attributes value table once its not valid or updated in BIOS. RBC should
|
||
|
|
clear pending attributes list whenever new attributes data received.
|
||
|
|
|
||
|
|
RBC daemon should preserve the AllBaseAttributes, PendingAttributes list in
|
||
|
|
non-volatile storage. PLDM daemon should preserve BIOS tables in non-volatile
|
||
|
|
storage. RBC and PLDM should restored the data whenever BMC reset.
|
||
|
|
|
||
|
|
#BIOS first boot
|
||
|
|
|
||
|
|
```
|
||
|
|
|
||
|
|
+--------------------------------------------------------------------------------------------------------------------+
|
||
|
|
| +-----------------------+ +---------------------------------------------------------------------------+|
|
||
|
|
| | BIOS | | BMC ||
|
||
|
|
| | | | +-------------------------------+ +-----------------------------+||
|
||
|
|
| | | | |PLDM Interface (MCTP) | |RBC Daemon Manager |||
|
||
|
|
| | | | | -Responsible for send /recv | |-Responsible for handle BIOS |||
|
||
|
|
| | | | | data between BIOS and BMC | | configuration attributes. |||
|
||
|
|
| | | | | | | -AllBaseAttributes |||
|
||
|
|
| | | | | | | -Pending Attributes |||
|
||
|
|
| | | | | | | -FactoryDefaultSetting |||
|
||
|
|
| | | | | | | -BIOSPwdHashData |||
|
||
|
|
+ +-----------------------+ | +-------------------------------+ +-----------------------------+||
|
||
|
|
| |Get the table info |<---Req-/Res--> | Provide the table information | | |||
|
||
|
|
| | & Check table Tag | | | | | |||
|
||
|
|
| |using GetBIOS table | | | | | |||
|
||
|
|
| | | | | | | |||
|
||
|
|
| |Set BIOS string table |<---Req-/Res--> | Get the string table | | |||
|
||
|
|
| | via Set BIOS table | | | | | |||
|
||
|
|
| |SetBIOSAttribute table |<---Req-/Res--> | Get the attributes table | | |||
|
||
|
|
| |SetBIOSAttributeValue |<---Req-/Res--> | Get the attributes value table| | |||
|
||
|
|
| |table via SetBIOStable | | | | | |||
|
||
|
|
| |table via SetBIOStable | | | | | |||
|
||
|
|
| |Init the BIOS config | | | Send the attributes data in | | |||
|
||
|
|
| |Based on value. | | | native to D-bus format |--dbus-->| AllBaseAttributes |||
|
||
|
|
| |via Set BIOS table | | | by Setting AllBaseAttributes | | |||
|
||
|
|
| | | | | | | |||
|
||
|
|
| | Continue the BIOS boot| | | | | |||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+||
|
||
|
|
| +---------------------------------------------------------------------------+|
|
||
|
|
+---------------------------------------+----------------------------------------------------------------------------+
|
||
|
|
|
||
|
|
|
||
|
|
#BIOS reset
|
||
|
|
+--------------------------------------------------------------------------------------------------------------------+
|
||
|
|
| +-----------------------+ +---------------------------------------------------------------------------+|
|
||
|
|
| | BIOS | | BMC ||
|
||
|
|
| | | | +-------------------------------+ +-----------------------------+||
|
||
|
|
| | | | |PLDM Interface (MCTP) | |RBC Daemon Manager |||
|
||
|
|
| | | | | -Responsible for send /recv | |-Responsible for handle BIOS |||
|
||
|
|
| | | | | data between BIOS and BMC | | configuration attributes. |||
|
||
|
|
| | | | | | | -AllBaseAttributes |||
|
||
|
|
| | | | | | | -Pending Attributes |||
|
||
|
|
| | | | | | | -FactoryDefaultSetting |||
|
||
|
|
| | | | | | | -BIOSPwdHashData |||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+||
|
||
|
|
| |Get the table info |<---Req-/Res--> | Provide the table information | | |||
|
||
|
|
| | & Check table Tag | | | | | |||
|
||
|
|
| |using GetBIOS table | | | | | |||
|
||
|
|
| | | | | | | |||
|
||
|
|
| | Get the Pending table |<---Req-/Res--> | Provide the Pending attributes| | |||
|
||
|
|
| | using Get BIOS table | | | table | | |||
|
||
|
|
| | | | | | | |||
|
||
|
|
| |SetBIOSAttributeValue |<---Req-/Res--> | Get the attributes table | | |||
|
||
|
|
| |table via SetBIOStable.| | | Delete the Pending attributes | | |||
|
||
|
|
| |Init the BIOS config | | | table | | |||
|
||
|
|
| |Based on value. | | | | | |||
|
||
|
|
| | | | | Send the attributes data in | | |||
|
||
|
|
| | | | | native to D-bus format by |--dbus-->| AllBaseAttributes |||
|
||
|
|
| | Reset the BIOS boot | | | setting AllBaseAttributes | | |||
|
||
|
|
| +-----------------------+ | +-------------------------------+ +-----------------------------+||
|
||
|
|
| +---------------------------------------------------------------------------+|
|
||
|
|
+---------------------------------------+----------------------------------------------------------------------------+
|
||
|
|
|
||
|
|
```
|
||
|
|
|
||
|
|
##Complete BIOS BMC flow for BIOS configuration in deferred update model
|
||
|
|
|
||
|
|
```
|
||
|
|
+----------------------------------------+ +----------------------------------------+
|
||
|
|
| BIOS | | BMC |
|
||
|
|
| | | |
|
||
|
|
| +----------------------------------+ | | +------------------------------------+ |
|
||
|
|
| | Send the BIOS capability Support| |--------KCS-------->| |1.Get the complete atttributes data.| |
|
||
|
|
| | Send the compressed BIOS file(or)| |-MCTP/KCS/Redfish-->| |2.Validate and convert into | |
|
||
|
|
| | Send PLDM data via MCTP (or) | | | | native to D-bus format. | |
|
||
|
|
| | Send the Redfish host interface | | | |3.Expose the D-bus interface | |
|
||
|
|
| +----------------------------------+ | | +------------------------------------+ |
|
||
|
|
| | | |
|
||
|
|
| +----------------------------------+ | | |
|
||
|
|
| | Get the file info & config status| <-Get config status-| |
|
||
|
|
| | - Any config changed or not | | | |
|
||
|
|
| | - File checksum in BMC | | | |
|
||
|
|
| | - New attribute values exist | | | |
|
||
|
|
| +----------------------------------+ | | |
|
||
|
|
| | | +-----------------------------------+ |
|
||
|
|
| +----------------------------------+ | | | | |
|
||
|
|
| | If new attribute value exist |<-|-----------------------| Send the new value attributes | |
|
||
|
|
| | then | | | | (Pending Attributes list) | |
|
||
|
|
| | Get & Update the BIOS variables | -| -----+ | | | |
|
||
|
|
| | | | | | +-----------------------------------+ |
|
||
|
|
| +---------------+------------------+ | | | |
|
||
|
|
| | | | | |
|
||
|
|
| YES | | | |
|
||
|
|
| | | | | +----------------------------------+ |
|
||
|
|
| +--------------V------------------+ | | | | | |
|
||
|
|
| | Send the updated data to BMC | | | | | Update the BIOS attributes | |
|
||
|
|
| | |------------------------->| (BaseBIOSTable) | |
|
||
|
|
| +---------------------------------+ | | | +----------------------------------+ |
|
||
|
|
| | | | |
|
||
|
|
| | | | |
|
||
|
|
| +---------------------------------+ | | | |
|
||
|
|
| | Reset the BIOS for BIOS conf | | NO | |
|
||
|
|
| | update | | | | |
|
||
|
|
| +---------------------------------+ | | | |
|
||
|
|
| | | | |
|
||
|
|
| +----------------------------------+ | | | |
|
||
|
|
| | Continue the BIOS boot | <-------+ | |
|
||
|
|
| +----------------------------------+ | | |
|
||
|
|
+----------------------------------------+ +----------------------------------------+
|
||
|
|
```
|
||
|
|
|
||
|
|
##Complete BIOS BMC flow for BIOS configuration in immediate update model
|
||
|
|
|
||
|
|
```
|
||
|
|
+----------------------------------------+ +----------------------------------------+
|
||
|
|
| BIOS | | BMC |
|
||
|
|
| | | |
|
||
|
|
| +----------------------------------+ | | +------------------------------------+ |
|
||
|
|
| | Send the BIOS capability Support| |--------KCS-------->| |1.Get the complete atttributes data | |
|
||
|
|
| | Send the compressed BIOS file(or)| |-MCTP/KCS/Redfish-->| |2.Validate and convert into | |
|
||
|
|
| | Send PLDM data via MCTP (or) | | | | native to D-bus format. | |
|
||
|
|
| | Send the Redfish host interface | | | |3.Expose the D-bus interface | |
|
||
|
|
| +----------------------------------+ | | +------------------------------------+ |
|
||
|
|
| | | |
|
||
|
|
| | | +------------------------------------+ |
|
||
|
|
| | | |PLDM can send complete all tables | |
|
||
|
|
| | | | & send the native to D-bus format | |
|
||
|
|
| | | | by Setting AllBaseAttributes | |
|
||
|
|
| | | +------------------------------------+ |
|
||
|
|
| | | +------------------------------------+ |
|
||
|
|
| | | | If attribute value changed then | |
|
||
|
|
| | | | Biosconfig send signal to PLDM. | |
|
||
|
|
| | | | PLDM read Pending attributes table | |
|
||
|
|
| | | | PLDM send the message to the host | |
|
||
|
|
| | | | PLDM send the data to the host | |
|
||
|
|
| | | +------------------------------------+ |
|
||
|
|
| +----------------------------------+ | | +------------------------------------+ |
|
||
|
|
| | Read the new Atributes value |<-|----------------------| Send new Pending attributes table | |
|
||
|
|
| | and | | | | | |
|
||
|
|
| | Update in the BIOS structure | | | +------------------------------------+ |
|
||
|
|
| +---------------+------------------+ | | |
|
||
|
|
| | | | |
|
||
|
|
| YES | | |
|
||
|
|
| | | | +-----------------------------------+ |
|
||
|
|
| +--------------V------------------+ | | | Update the BIOS atrributes data. | |
|
||
|
|
| | Send the updated data to BMC | | | | Discard the Pending attributes | |
|
||
|
|
| | |------------------------>| table | |
|
||
|
|
| +---------------------------------+ | | +-----------------------------------+ |
|
||
|
|
| | | |
|
||
|
|
+----------------------------------------+ +----------------------------------------+
|
||
|
|
```
|
||
|
|
|
||
|
|
RBC should create the Pending Attribute list whenever SetPendingAttributes &
|
||
|
|
SetAttribute Method called and raise the PendingAttributesUpdated signal. RBC
|
||
|
|
should preserve the Pending Attributes list across the BMC reset and RBC should
|
||
|
|
clear the Pending Attributes list whenever new AllBaseBIOSTables received from
|
||
|
|
BIOS.
|
||
|
|
|
||
|
|
#Redfish interfaces for remote Bios configuration
|
||
|
|
|
||
|
|
```
|
||
|
|
+-----------------------------------------------------------------------------------------------------------+
|
||
|
|
| +-------------------------+ +----------------------------------------------------------------+|
|
||
|
|
| | RBC Web tool - POSTMAN | | BMC ||
|
||
|
|
| | (Please refer the | | +-----------------------+ +---------------------------+ ||
|
||
|
|
| | below redfish example | | |Redfish Daemon | |RBC Daemon Manager | ||
|
||
|
|
| | for each request) | | |-Responsible for handle| |-Parse Bios Data,convert to| ||
|
||
|
|
| | | | |all Redfish request | | required format & return | ||
|
||
|
|
| | | | +-----------------------+ +---------------------------+ ||
|
||
|
|
| +-------------------------+ | +-----------------------+ +---------------------------+ ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |1.Get Current attributes |<---Req-/Res--> | Read BaseBIOSTable |<-dbus-| BaseBIOSTable | ||
|
||
|
|
| | name & value list | | | | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |2.Get Attribute Registry |<---Req-/Res--> | Read BaseBIOSTable |<-dbus-| BaseBIOSTable | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |3.Change BIOS Password |<---Req-/Res--> | Call RBC D-bus Method |-dbus->| ChangePassword() | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |4.Reset To default |<---Req-/Res--> | Set ResetBIOSSettings |-dbus->| ResetBiosSettings | ||
|
||
|
|
| | settings | | | | | -ResetFlag | ||
|
||
|
|
| |5.Update new BIOS setting|<---Req-/Res--->| Call RBC D-bus Method |-dbus->| SetAttribute() | ||
|
||
|
|
| | (For single attribute) | | | | | | ||
|
||
|
|
| | | | | | | | ||
|
||
|
|
| |6.Get Pending attributes |<---Req-/Res--->| Get PendingAttributes |<-dbus-| PendingAttributes | ||
|
||
|
|
| | list | | | | | | ||
|
||
|
|
| |7.Update new BIOS setting|<---Req-/Res--->| Set PendingAttributes |<-dbus-| PendingAttributes | ||
|
||
|
|
| | list | | | | | | ||
|
||
|
|
| | For multiple attributes| | | | | | ||
|
||
|
|
| +-------------------------+ | +-----------------------+ +---------------------------+ ||
|
||
|
|
| +---------------------------------------------------------------+||
|
||
|
|
+-----------------------------------------+-----------------------------------------------------------------+
|
||
|
|
```
|
||
|
|
|
||
|
|
1. Get Current Attributes name and value list: Get the current BIOS settings
|
||
|
|
attribute name and value pair list. GET Method -
|
||
|
|
"https://<BMC IP address>/redfish/v1/Systems/system/Bios"
|
||
|
|
|
||
|
|
2. Get Attribute Registry: Get the detailed information about Bios Attribute
|
||
|
|
like current value, supported value, description, Menupath, Default value.
|
||
|
|
GET Method - "https://<BMC IP address>/redfish/v1/Registries/Bios"
|
||
|
|
|
||
|
|
3. Change BIOS password: ACTION -
|
||
|
|
"https://<BMC IP address>/redfish/v1/Systems/system/Bios/Actions/Bios.ChangePassword"
|
||
|
|
|
||
|
|
4. Reset To default settings: ACTION -
|
||
|
|
"https://<BMC IP address>/redfish/v1/Systems/system/Bios/Actions/Bios.ResetBios"
|
||
|
|
|
||
|
|
5. Update new BIOS settings (single attribute): Use to send the new value for
|
||
|
|
particular attribute or list of attributes. PATCH Method -
|
||
|
|
"https://<BMC IP address>/redfish/v1/Systems/system/Bios/Settings" Ex:
|
||
|
|
Attribute name and new value : { "DdrFreqLimit" : 2400}
|
||
|
|
|
||
|
|
6. Get the new pending value list: Use to get the new pending attributes list.
|
||
|
|
GET Method -
|
||
|
|
"https://<BMC IP address>/redfish/v1/Systems/system/Bios/Settings" -Valid
|
||
|
|
only in deferred model. For immediate update model, It will be empty. Ex:
|
||
|
|
Attribute name and new value : { "DdrFreqLimit" : 2400,"QuietBoot",0x1 }
|
||
|
|
|
||
|
|
7. Update new BIOS settings (multiple attributes): Use to send the new value for
|
||
|
|
particular attribute or list of attributes. PATCH Method -
|
||
|
|
"https://<BMC IP address>/redfish/v1/Systems/system/Bios/Settings" Ex:
|
||
|
|
Attribute name and new value list : { "DdrFreqLimit" : 2400},"QuietBoot",0x1
|
||
|
|
}
|
||
|
|
|
||
|
|
## Alternatives Considered
|
||
|
|
|
||
|
|
Redfish Host specification definition is not completed and ready BIOS support
|
||
|
|
also not available. There are 1000+ BIOS variables and storing in
|
||
|
|
phosphor-settingsd is not optimal.
|
||
|
|
|
||
|
|
## Impacts
|
||
|
|
|
||
|
|
BIOS must support and follow RBC BIOS configuration flow.
|
||
|
|
|
||
|
|
## Testing
|
||
|
|
|
||
|
|
Able to change the BIOS configuration via BMC through LAN Able to change the
|
||
|
|
BIOS setup password via BMC Compliance with Redfish will be tested using the
|
||
|
|
Redfish Service Validator
|